Always remember that the ASHP (air-source heat pump) must contain the correct refrigerant charge to be able to transfer heat appropriately and meet the structure needs.
Only liquids and solids can be sub cooled. Sub cooling is any temperature of a liquid or solid below its saturation temperature. As an example, consider water. Liquid water at sea level and atmospheric pressure (14.7 PSI) has a saturation (boiling) temperature of 212ºF. At this boiling temperature (and pressure) and above, the water will be in a vapor state (or “superheated”). At any temperature below 212ºF (and atmospheric pressure in this case), the water would be in a liquid state. The resulting temperature of the water would be below the boiling temperature for water of 212ºF. If the water was at 200ºF, we would say that it is actually sub cooled 12 degrees. Liquid refrigerant can be under the same situation within an operating heat pump. In the condenser (the indoor coil during winter), after the vapor refrigerant condenses to a liquid, it will continue to decrease in temperature as more heat is rejected, or be sub cooled.
· First, purge your manifold gauge lines. Then, connect the gauge manifold to the base-valve service ports. Run the ASHP at least 10 minutes in the heating mode to allow pressures to stabilize. Install a reliable temperature analyzer (thermometer) on the liquid line leaving the indoor coil with adequate contact and insulate for the best possible reading.
· Measure and record the outdoor ambient temperature with a reliable temperature analyzer.
· Measure the entering dry bulb temperature at the indoor coil (at the return grille). Use manufacturers’ extended performance data to determine the pressures expected at the inspection conditions (heating mode). You should be within ± 5 PSIG if the system is correctly charged.
When charging an R-410A system, you must charge from the refrigerant cylinder in the liquid form (pull the liquid from the canister in the upside-down position), and charge into the low side of the system. Throttle the refrigerant to a vapor either by “hand-throttling” using the hand valve and the compound gauge, or use a commercially available throttling device in the low side line. This method assures the zeotropic blends in the R-410A refrigerant will not fractionate, and is required by the EPA and UL.
Evaporative Cooling
Evaporative cooling is a process that uses the effect of evaporation as a natural heat sink. Sensible heat from the air is absorbed to be used as latent heat necessary to evaporate water. The amount of sensible heat absorbed depends on the amount of water that can be evaporated.
Evaporative cooling can be direct or indirect; passive or hybrid. In direct evaporative cooling, the water content of the cooled air increases because air is in contact with the evaporated water. In indirect evaporative cooling, evaporation occurs inside a heat exchanger and the water content of the cooled air remains unchanged. Since high evaporation rates might increase relative humidity and create discomfort, direct evaporative cooling can be applied only in places where relative humidity is very low.
Where evaporation occurs naturally it is called passive evaporation. A space can be cooled by passive evaporation where there are surfaces of still or flowing water, such as basins or fountains. Where evaporation has to be controlled by means of some mechanical device, the system is called a hybrid evaporative system.
Evaporative Cooling
Evaporative cooling is a process that uses the effect of evaporation as a natural heat sink. Sensible heat from the air is absorbed to be used as latent heat necessary to evaporate water. The amount of sensible heat absorbed depends on the amount of water that can be evaporated.
Evaporative cooling can be direct or indirect; passive or hybrid. In direct evaporative cooling, the water content of the cooled air increases because air is in contact with the evaporated water. In indirect evaporative cooling, evaporation occurs inside a heat exchanger and the water content of the cooled air remains unchanged. Since high evaporation rates might increase relative humidity and create discomfort, direct evaporative cooling can be applied only in places where relative humidity is very low.
Where evaporation occurs naturally it is called passive evaporation. A space can be cooled by passive evaporation where there are surfaces of still or flowing water, such as basins or fountains. Where evaporation has to be controlled by means of some mechanical device, the system is called a hybrid evaporative system.
Evaporative cooling is based on the thermodynamics of evaporation of water, i.e. the change of the liquid phase of water into water vapor. This phase change requires energy, which is called latent heat of evaporation- this is the energy required to change a substance from liquid phase to the gaseous one without temperature change. When non- saturated air (i.e. air that does not contain liquid water but only water vapor) comes in direct contact with water evaporation occurs. It is obvious that during this process the moisture content of air is increased. This process is represented on the psychometric chart by a displacement along a constant wet bulb line, AB. The air to be cooled is initially at point A. The air, as a result of the direct evaporative cooling process, reaches point B. This is a constant wet bulb temperature process and therefore line AB is parallel to the wet bulb temperature lines.
When evaporation occurs in the primary circuit of a heat exchanger, while the air to be cooled circulates in the secondary circuit, the air temperature decreases but its humidity ratio remains constant. It must be noted that since the air temperature drops, its relative humidity will increase, but less than during the direct evaporative cooling process. Since the humidity ratio of the air does not change, this process is represented on the psychometric chart by a displacement along a constant humidity ratio line CD. In this figure, the air to be cooled, initially at point C is sensibly cooled by the indirect evaporative cooler until it reaches point B.
Evaporative cooling uses large volumes or air. Forcing this volume of air through small ducts, around sharp corners, and out of small outlets, involves ducting costs. In some cases the best duct system is none. Just blow the air into a large daytime occupancy rooms.
If not properly designed direct type evaporative coolers may pose the following problems:
- The cooled air may be excessively humid.
- The high rate of air flow and large number of air changes, which are necessary for effective cooling, cause large variation in the air speed and the associated thermal sensation within the cooled space. This results in a waste of energy, which has been used to cool the discharged air.
Indirect type evaporative coolers try to overcome these defects. Since the air in these types of coolers gets cooled without coming in direct contact with water, the problem of excessive humidity in the room air gets automatically solved. Simultaneously the required number of air changes also gets reduced.
The important advantages of the indirect type evaporative cooling are as follows:
- Depending upon the performance of the system used, the operating cost gets reduced by 20% - 60% below that of refrigerant air conditioning. Of course, the temperature achieved by evaporative cooling is higher and varying unlike air conditioned system.
- Power consumption is less resulting in a sharp reduction in the running costs. Because of this reason, the indirect evaporative coolers can also be used where electricity is expensive or scarce.
- It can be used as a precooler for refrigerant air conditioning systems.
- In this type of cooling, the exhaust room air can be delivered to the cooling tower as a result of which the lower water temperature is obtained. This in turn, produces more cooling.